Security & Threat Intelligence · 13.08.2026, 16:55 UTC
Haiwell IoT Cloud HMI Gateway
| Schweregrad | info |
|---|---|
| CVE | ↗ |
| Kategorie | Security & Threat Intelligence |
| Quelle | CISA Advisories ↗ |
| Veröffentlicht | 13.08.2026 UTC |
Sicherheitsmeldung mit Schweregrad noch nicht bewertet. Betroffene Kennungen: CVE-2026-19188. Technische Details im Tab „Originaltext“; empfohlene Schritte in der Checkliste.
View CSAF Summary Successful exploitation of this vulnerability may allow an attacker to inject and execute arbitrary OS commands with root privileges. The following versions of Haiwell IoT Cloud HMI Gateway are affected:
Haiwell IoT Cloud HMI Gateway 3.40.1.12 (CVE-2026-19188)
CVSS Vendor Equipment Vulnerabilities
v3 10 Haiwell Haiwell IoT Cloud HMI Gateway Improper Neutralization of Special Elements used in an OS Command ('OS Command Injection')
Background
Critical Infrastructure Sectors: Energy, Critical Manufacturing, Water and Wastewater Countries/Areas Deployed: Worldwide Company Headquarters Location: China
Vulnerabilities
Expand All +
CVE-2026-19188
A critical OS command injection vulnerability has been identified in the Haiwell IoT Cloud HMI Gateway product. The vulnerability exists in the Net Check feature accessible via the /setting endpoint. The cmdPing Socket.io event fails to properly sanitize user-supplied input before passing it to the underlying operating system, allowing an attacker to inject and execute arbitrary OS commands with root privileges View CVE Details
Affected Products Haiwell IoT Cloud HMI Gateway
Vendor:Haiwell Product Version:Haiwell Haiwell IoT Cloud HMI Gateway: 3.40.1.12 Product Status:known_affected
Remediations MitigationHaiwell has addressed the issue in patch version number Scada-v3.50.1.19, which is available for download on their website: …