Sicherheitsmeldung mit Schweregrad noch nicht bewertet. Betroffene Kennungen: CVE-2026-58115. Technische Details im Tab „Originaltext“; empfohlene Schritte in der Checkliste.
View CSAF Summary SIMATIC IoT2050 Advanced devices running Industrial OS with Node-RED installed contain a missing authentication vulnerability in the Node-RED HTTP interface that could allow an unauthenticated remote attacker to create malicious flows and execute arbitrary code on the underlying server with maximum privileges. Siemens has released a new version for SIMATIC IoT2050 Advanced and strongly recommends to update to the latest version. The following versions of Siemens SIMATIC IoT2050 Advanced are affected:
SIMATIC IoT2050 Advanced (6ES7647-0BA00-1YA2) vers:intdot/<4.3.4.1
CVSS Vendor Equipment Vulnerabilities
v3 10 Siemens Siemens SIMATIC IoT2050 Advanced Missing Authentication for Critical Function
Background
Critical Infrastructure Sectors: Chemical, Critical Manufacturing, Energy, Transportation Systems Countries/Areas Deployed: Worldwide Company Headquarters Location: Germany
Vulnerabilities
Expand All +
CVE-2026-58115
Affected devices do not enforce authentication on the Node-RED HTTP interface, allowing unauthenticated access to programming nodes that are capable of executing system commands on the server. This could allow an unauthenticated remote attacker to create malicious flows through the HTTP interface in order to execute arbitrary code on the underlying server with maximum privileges. View CVE Details
Affected Products Siemens SIMATIC IoT2050 Advanced
Vendor:Siemens Product Version:SIMATIC IoT2050 Advanced (6ES7647-0BA00-1YA2) < V4.3.4.1 running Industrial OS with Node-RED installed Product …